Catalog item

CIRCUIT BREAKER

5925FSC
00NCB code
120-9366Item number
NIIN 00-120-9366
Request a quote
Unit price
$180.25
Unit of issue
EA
Source of supply
SMS
DEMIL code
A

Identification

Item name code
00136
PINC
0000136
Criticality code
X
II
0
DEMIL code
A
DEMIL integrity code
1
NIIN assigned
21-OCT-68
Precious metals indicator
U
Hazardous material indicator
P
Schedule B export code
8536200040
FedMall
Y

Management

Effective date
01-OCT-2026
Major organizational entity
DS
Acquisition advice code
X
Source of supply
SMS
Unit of issue
EA
Unit of measure quantity
0.0000
Unit price
$180.25
Quantity per unit pack
1
Controlled inventory item code
U
Shelf-life code
0
Management control
-------
Net price
$0.00
USC
I

Part numbers

Part numberCAGECAGE statusRNCCRNVCDocument availability codeRNAACRNFCRNSCSADC
EA3015V11660
WESTINGHOUSE ELECTRIC CORP CONTROL BUSINESS UNIT
H39ETX3D
EB3015V11660
WESTINGHOUSE ELECTRIC CORP CONTROL BUSINESS UNIT
HC16ZZAC
S177425811660
WESTINGHOUSE ELECTRIC CORP CONTROL BUSINESS UNIT
H595HD1B

Characteristics

BODY STYLE
BODY LENGTHINCHES NOMINAL 6.000
BODY WIDTHINCHES NOMINAL 4.125
BODY HEIGHTINCHES NOMINAL 3.375
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 5.062
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 1.375
UNTHREADED MOUNTING HOLE DIAMETERINCHES NOMINAL 0.196
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 4.500
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES NOMINAL 1.375
BOSS HEIGHTINCHES NOMINAL 0.125
POLE QUANTITY3
MOUNTING FACILITY TYPE AND QUANTITYUNTHREADED HOLE(S) 4
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 15.0 AND AMPERES DC 15.0
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 240.0 AND DC 125.0
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 10000.0 AND DC 5000.0
CIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
TRIP RELEASE METHODALL LOCATIONS THERMAL-MAGNETIC
TRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
RESET METHODMANUAL
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 29.000 AND MAXIMUM AT 200 PCT 120.000
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT
TRIP RELEASE AMBIENT TEMP RATINGALL LOCATIONS CELSIUS NOMINAL 50.0
FREQUENCY IN HERTZ60.0
MATERIALCASE PLASTIC
TERMINAL TYPE AND QUANTITYCOMPRESSION 6

MOE rules

MOE rule
DGX1
MOE CD
DS
AMC
0
AMSC
0
Date assigned
01-NOV-25
PICA
GX
PICA LOA
01
Auth collab
GX

Freight

ACTY CD
ZQ
NMFC
061700
NMFC sub
Z
Uniform freight class
34580
Less than truckload
W
Water commodity code
72D
Type of cargo code
Z
Special handling code
9
Air dimension code
A
Air commodity code
HZ
NMF description
ELEC APPLIANCES/INSTRUMENTS NOI

Related items

Standardization

Item standardization code
2
Orig stdzn dec
TX
Dt stdzn dec
17-MAR-1969
NIIN status code
0

Request a quote

Your request goes to A-DEFENSE, a US Defense supplier in Texas, who will reply by email.