Request a quoteCIRCUIT BREAKER
5925FSC
00NCB code
227-0394Item number
NIIN 00-227-0394
- DEMIL code
- A
Identification
- Item name code
- 00136
- PINC
- 0000136
- Criticality code
- X
- II
- 0
- DEMIL code
- A
- DEMIL integrity code
- 1
- NIIN assigned
- 01-JAN-63
- Precious metals indicator
- U
- Hazardous material indicator
- P
- Schedule B export code
- 8536200040
- Last known source of supply
- S9E
Part numbers
- Part number
- PDLM120
- CAGE
- 82647SENSATA TECHNOLOGIES, INC. DIV SENSATA ATTLEBORO
- CAGE status
- A
- RNCC
- 3
- RNVC
- 2
- Document availability code
- E
- RNAAC
- TX
- RNFC
- 3
- RNSC
- D
Characteristics
| POLE QUANTITY | 1 |
|---|---|
| MOUNTING SURFACE TO TERMINAL END DISTANCE | INCHES NOMINAL 1.109 |
| FRAGILITY FACTOR | MODERATELY RUGGED |
| UNTHREADED MOUNTING HOLE DIAMETER | INCHES NOMINAL 0.190 |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | INCHES NOMINAL 2.406 |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES NOMINAL 1.062 |
| MATERIAL | CASE PLASTIC |
| TERMINAL TYPE AND QUANTITY | SCREW 2 |
| BODY WIDTH | INCHES NOMINAL 1.875 |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| MOUNTING FACILITY TYPE AND QUANTITY | UNTHREADED HOLE(S) 2 |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | SINGLE LOCATION AMPERES AC 120.0 AND AMPERES DC 120.0 |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | SINGLE LOCATION AC 120.0 AND DC 30.0 |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | SINGLE LOCATION AC 875.0 AND DC 875.0 |
| CIRCUIT PROTECTION TYPE | SINGLE LOCATION OVERCURRENT |
| TRIP RELEASE METHOD | SINGLE LOCATION THERMAL |
| TRIP RELEASE CHARACTERISTIC | SINGLE LOCATION TIME DELAY |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 |
| RESET METHOD | MANUAL |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | PUSH BUTTON 1 |
| ACTUATOR FUNCTION | RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| INTERNAL TRIP RELEASE CONFIGURATION | SINGLE LOCATION SERIES TRIP |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | SINGLE LOCATION MINIMUM AT 200 PCT 20.000 AND MAXIMUM AT 200 PCT 150.000 |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | SHOCKPROOF |
| TRIP RELEASE AMBIENT TEMP RATING | SINGLE LOCATION FAHRENHEIT NOMINAL 77.0 |
| UNPACKAGED UNIT WEIGHT | OUNCES NOMINAL 5.000 |
| FREQUENCY IN HERTZ | 60.0 |
| BODY STYLE | |
| OVERALL LENGTH | INCHES NOMINAL 3.156 |
MOE rules
| MOE rule | MOE CD | Date assigned | PICA | PICA LOA | Auth collab |
|---|---|---|---|---|---|
| WB01 | WB | 01-FEB-05 | WB | 81 | WB |
| ZP01 | ZP | 01-APR-91 | ZP | 81 | ZP |
| ZR01 | ZR | 01-JUL-97 | ZR | 81 | ZR |
| ZU01 | ZU | 01-APR-91 | ZU | 81 | ZU |
| ZW01 | ZW | 01-NOV-98 | ZW | 81 | ZW |
Freight
- ACTY CD
- XX
Related items
Standardization
- Item standardization code
- 3
- Orig stdzn dec
- TX
- Dt stdzn dec
- 15-FEB-1969
- NIIN status code
- 0