Catalog item

CIRCUIT BREAKER

5925FSC
00NCB code
248-5734Item number
NIIN 00-248-5734
Request a quote
DEMIL code
A

Identification

Item name code
00136
PINC
0000136
Criticality code
X
II
0
DEMIL code
A
DEMIL integrity code
1
NIIN assigned
10-SEP-72
Precious metals indicator
U
Hazardous material indicator
P
Schedule B export code
8536200040
Last known source of supply
S9E

Part numbers

Part numberCAGECAGE statusRNCCRNVCDocument availability codeRNAACRNFCRNSC
SM33HK8-240VAC400C274193
EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
HC15TX3D
HB2Z2-10974193
EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
HC15TX3D
MILC39019-481349
MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
A413TX3D
M39019-4-10981349
MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
A223TX3D
AP12-1R4-1-80281541
SENSATA TECHNOLOGIES MARYLAND, INC
AC15TX3D

Characteristics

OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 240.0
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 300.0
BODY STYLE
BUSHING LENGTHINCHES MAXIMUM 0.380
BODY LENGTHINCHES MAXIMUM 1.562
BODY WIDTHINCHES MAXIMUM 1.281
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MAXIMUM 0.906
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 0.625
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
FRAGILITY FACTORMODERATELY RUGGED
MOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MAXIMUM 1.828
POLE QUANTITY2
ARC QUENCHING METHODMAGNETIC BLOWOUT
RESET METHODMANUAL
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONBETWEEN POLE ONE AND TWO
TERMINAL TYPE AND QUANTITYWIRE HOOK 4
SPECIFICATION/STANDARD DATAGOVERNMENT SPECIFICATION 81349--IL-C-39019 TO 4
MOUNTING FACILITY TYPE AND QUANTITYTHREADED BUSHING WITH PANEL SEAL 1
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SPECIAL HANDLING FEATUREMAGNETIC
THREAD QUANTITY PER INCH32
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 8.0
THREAD SERIES DESIGNATORUNEF
CIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
TRIP RELEASE METHODALL LOCATIONS MAGNETIC
SWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE TWO
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 0.055 AND MAXIMUM AT 200 PCT 0.950
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDHERMETICALLY SEALED
SWITCH TERMINAL TYPEPIN
SWITCH CURRENT RATING AND TYPE IN AMPSAC 0.5 AND DC 0.5
SWITCH VOLTAGE RATING AND TYPE IN VOLTSAC 120.0 AND DC 50.0
FREQUENCY IN HERTZ400.0
TEST DATA DOCUMENTSPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). 81349--IL-C-39019
TRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT115.0
INTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
NOMINAL THREAD SIZEINCHES 0.375
AUXILIARY SWITCH FUNCTION AND QUANTITYALARM 1

MOE rules

MOE rule
ZP01
MOE CD
ZP
Date assigned
01-APR-91
PICA
ZP
PICA LOA
81
Auth collab
ZP

Freight

ACTY CD
TX

Related items

Standardization

Item standardization code
E
Orig stdzn dec
TX
Dt stdzn dec
23-DEC-1976
NIIN status code
0

Request a quote

Your request goes to A-DEFENSE, a US Defense supplier in Texas, who will reply by email.