Catalog item

CIRCUIT BREAKER

5925FSC
00NCB code
453-5026Item number
NIIN 00-453-5026
Request a quote
DEMIL code
A

Identification

Item name code
00136
PINC
0000136
Criticality code
X
II
0
DEMIL code
A
DEMIL integrity code
1
NIIN assigned
14-APR-69
Precious metals indicator
A
Hazardous material indicator
P
Schedule B export code
8536200040
Last known source of supply
S9E

Part numbers

Part numberCAGECAGE statusRNCCRNVCDocument availability codeRNAACRNFCRNSC
MILC39019+1B5881349
MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
A593TX4B
MIL-C-39019/181349
MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
A41EZZ
M39019/01-5881349
MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
A22EZZ

Characteristics

TEST DATA DOCUMENTSPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). 81349--IL-C-39019
TRIP RELEASE METHODSINGLE LOCATION MAGNETIC
THREAD SERIES DESIGNATORUNEF
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CIRCUIT PROTECTION TYPESINGLE LOCATION OVERCURRENT
RESET METHODMANUAL
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
ULTIMATE TRIP TIME PER POLE IN SECONDSSINGLE LOCATION MINIMUM 3.000 AND MAXIMUM 60.000
BODY WIDTHINCHES MAXIMUM 0.625
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MAXIMUM 0.906
TRIP RELEASE CHARACTERISTICSINGLE LOCATION TIME DELAY
SPECIFICATION/STANDARD DATAGOVERNMENT SPECIFICATION 81349--IL-C-39019 TO 01
BUSHING LENGTHINCHES MAXIMUM 0.380
POLE QUANTITY1
MOUNTING FACILITY TYPE AND QUANTITYTHREADED BUSHING 1
THREAD QUANTITY PER INCH32
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLESINGLE LOCATION AMPERES AC 10.0
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSSINGLE LOCATION AC 240.0
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSSINGLE LOCATION AC 300.0
TERMINAL TYPE AND QUANTITYWIRE HOOK 2
BODY STYLE
INTERNAL TRIP RELEASE CONFIGURATIONSINGLE LOCATION SERIES TRIP
NOMINAL THREAD SIZEINCHES 0.375
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTSINGLE LOCATION MINIMUM AT 200 PCT 0.500 AND MAXIMUM AT 200 PCT 0.900
MOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MAXIMUM 1.700
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND HERMETICALLY SEALED
FREQUENCY IN HERTZ60.0
BODY LENGTHINCHES MAXIMUM 1.562

MOE rules

MOE ruleMOE CDDate assignedPICAPICA LOAAuth collab
YB01YB01-SEP-08YB81YB
ZH01ZH01-APR-91ZH81ZH
ZW01ZW01-NOV-05ZW81ZW

Freight

ACTY CD
TX
NMFC
061700
NMFC sub
Z
Uniform freight class
34580
Less than truckload
W
Water commodity code
658
Type of cargo code
Z
Special handling code
9
Air dimension code
A
Air commodity code
HZ
NMF description
ELEC APPLIANCES/INSTRUMENTS NOI

Related items

Standardization

Item standardization code
E
Orig stdzn dec
TX
Dt stdzn dec
06-JAN-1977
NIIN status code
0

Request a quote

Your request goes to A-DEFENSE, a US Defense supplier in Texas, who will reply by email.