Catalog item

CIRCUIT BREAKER

5925FSC
00NCB code
501-9687Item number
NIIN 00-501-9687
Request a quote
DEMIL code
A

Identification

Item name code
00136
PINC
0000136
Criticality code
N
II
0
DEMIL code
A
DEMIL integrity code
1
NIIN assigned
01-JAN-63
Precious metals indicator
A
ADP equipment code
0
Hazardous material indicator
P
Schedule B export code
8536200040
Last known source of supply
NRP

Part numbers

Part numberCAGECAGE statusRNCCRNVCDocument availability codeRNAACRNFCRNSC
305279PC75ATRIP30086
L3HARRIS MARITIME POWER & ENERGY SOLUTIONS, INC. DBA SPD ELECTRICAL SYSTEMS, INC.
A325XX3D
305279-75AMP30086
L3HARRIS MARITIME POWER & ENERGY SOLUTIONS, INC. DBA SPD ELECTRICAL SYSTEMS, INC.
A521HD1B
ET5621530086
L3HARRIS MARITIME POWER & ENERGY SOLUTIONS, INC. DBA SPD ELECTRICAL SYSTEMS, INC.
A325XX3D
90028-6202-2298ALT4PC75ATRIP80064
NAVAL SHIP SYSTEMS COMMAND
A325XX3D
574-6201-810907REVDPC3280064
NAVAL SHIP SYSTEMS COMMAND
A325XX3D
MILC1736181349
MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
A414HD3D

Characteristics

DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 8.750
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES NOMINAL 1.625
BODY LENGTHINCHES NOMINAL 10.000
BODY WIDTHINCHES NOMINAL 5.000
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 8.750
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 1.625
BODY STYLE
TRIP RELEASE CHARACTERISTICALL LOCATIONS INSTANTANEOUS AND TIME DELAY
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT600.0
RESET METHODMANUAL
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
ACTUATOR FUNCTIONTRIP-RESET
BOSS HEIGHTINCHES NOMINAL 0.188
MOUNTING SURFACE TO TERMINAL END DISTANCEINCHES NOMINAL 8.625
POLE QUANTITY3
MOUNTING FACILITY TYPE AND QUANTITYTHREADED STUD(S) 6
FEATURES PROVIDEDINTERCHANGEABLE TRIP RELEASE
THREAD QUANTITY PER INCH16
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 75.0 AND AMPERES DC 75.0
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 500.0 AND DC 250.0
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 15000.0 AND DC 10000.0
CIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
TRIP RELEASE METHODALL LOCATIONS THERMAL
MATERIALCASE PLASTIC
THREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TERMINAL TYPE AND QUANTITYTHREADED STUD 6
NONDEFINITIVE SPEC/STD DATATYPE AQBA100
FREQUENCY IN HERTZ60.0
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS NOMINAL AT 500 PCT 25.000
TRIP RELEASE AMBIENT TEMP RATINGALL LOCATIONS CELSIUS NOMINAL 50.0
NOMINAL THREAD SIZEINCHES 0.375
INTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
ACTUATOR POSITION DESIGNATIONAT EACH POLE

MOE rules

MOE rule
ZW01
MOE CD
ZW
Date assigned
01-NOV-98
PICA
ZW
PICA LOA
81
Auth collab
ZW

Freight

ACTY CD
XX
NMFC
061700
NMFC sub
Z
Uniform freight class
34580
Less than truckload
W
Less than carload
P
Water commodity code
658
Type of cargo code
Z
Special handling code
9
Air dimension code
A
Air commodity code
HZ
NMF description
ELEC APPLIANCES/INSTRUMENTS NOI

Related items

Standardization

Item standardization code
2
Orig stdzn dec
TX
Dt stdzn dec
15-DEC-1974
NIIN status code
0

Request a quote