Catalog item

CIRCUIT BREAKER

5925FSC
00NCB code
584-6242Item number
NIIN 00-584-6242
Request a quote
DEMIL code
A

Identification

Item name code
00136
PINC
0000136
Criticality code
X
II
0
DEMIL code
A
DEMIL integrity code
1
NIIN assigned
21-DEC-74
Precious metals indicator
U
Hazardous material indicator
P
Schedule B export code
8536200040
Last known source of supply
S9E

Part numbers

Part numberCAGECAGE statusRNCCRNVCDocument availability codeRNAACRNFCRNSC
4004040-0536378
RAYTHEON TECHNICAL SERVICES COMPANY
R5929ZB
AM3A3A20-274193
EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
H3949Z3D

Characteristics

INTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
ACTUATOR POSITION DESIGNATIONAT EACH POLE
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 2.000 AND MAXIMUM AT 200 PCT 20.000 AND MINIMUM AT 400 PCT 0.300 AND MAXIMUM AT 400 PCT 2.000
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 0.750
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 2.062
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES NOMINAL 0.750
BOSS HEIGHTINCHES NOMINAL 0.140
MOUNTING SURFACE TO TERMINAL END DISTANCEINCHES NOMINAL 2.533
POLE QUANTITY3
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 240.0
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 1000.0
CIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
TRIP RELEASE METHODALL LOCATIONS MAGNETIC-HYDRAULIC
TRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
ULTIMATE TRIP TIME PER POLE IN SECONDSALL LOCATIONS MINIMUM 9.000 AND MAXIMUM 120.000
RESET METHODMANUAL
FREQUENCY IN HERTZ60.0
MATERIALCASE PLASTIC
NOMINAL THREAD SIZEINCHES 0.138
BODY WIDTHINCHES NOMINAL 2.500
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND MOISTURE RESISTANT
THREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TERMINAL TYPE AND QUANTITYTHREADED STUD 6
MOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 6
THREAD QUANTITY PER INCH32
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 20.0
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 1.938
ACTUATOR FUNCTIONTRIP-RESET
BODY STYLE
BODY LENGTHINCHES NOMINAL 2.500
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 3

MOE rules

MOE ruleMOE CDDate assignedPICAPICA LOAAuth collab
ZC01ZC01-APR-91ZC81ZC
ZH01ZH01-APR-91ZH81ZH
ZR01ZR01-DEC-07ZR81ZR
ZT01ZT01-APR-91ZT81ZT
ZU01ZU01-APR-08ZU81ZU
ZW01ZW01-NOV-05ZW81ZW

Freight

ACTY CD
ZG
NMFC
061700
NMFC sub
Z
Uniform freight class
34580
Less than truckload
W
Less than carload
P
Water commodity code
658
Type of cargo code
Z
Special handling code
9
Air dimension code
A
Air commodity code
HZ
NMF description
ELEC APPLIANCES/INSTRUMENTS NOI

Related items

Standardization

Item standardization code
3
Orig stdzn dec
TX
Dt stdzn dec
15-FEB-1980
NIIN status code
0

Request a quote