Catalog item

CIRCUIT BREAKER

5925FSC
00NCB code
791-4058Item number
NIIN 00-791-4058
Request a quote
DEMIL code
A

Identification

Item name code
00136
PINC
0000136
Criticality code
X
II
0
DEMIL code
A
DEMIL integrity code
1
NIIN assigned
03-MAY-68
Precious metals indicator
U
Hazardous material indicator
P
Schedule B export code
8536200040
Last known source of supply
S9E

Part numbers

Part numberCAGECAGE statusRNCCRNVCDocument availability codeRNAACRNFCRNSC
3XAM1516HK2-5-416VAC400-474193
EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
H59ETX1D
9176288-274193
EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
H596TX4D
9176288-218876
US ARMY AVIATION AND MISSILE COMMAND
A32ATX3D

Characteristics

CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MINIMUM 3.053 AND INCHES MAXIMUM 3.073
FREQUENCY IN HERTZ400.0
MATERIALCASE PLASTIC
TRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
SWITCH VOLTAGE RATING AND TYPE IN VOLTSAC 250.0 AND DC 50.0
SWITCH CURRENT RATING AND TYPE IN AMPSAC 5.0 AND DC 1.0
BODY STYLE
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 3.500 AND MAXIMUM AT 200 PCT 10.000
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF AND FUNGUS PROOF
ACTUATOR FUNCTIONTRIP-RESET
SWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE ONE
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SWITCH TERMINAL TYPETAB, SOLDER LUG
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 3
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 2000.0
CIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
TRIP RELEASE METHODALL LOCATIONS MAGNETIC-HYDRAULIC
THREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TERMINAL TYPE AND QUANTITYTHREADED STUD 6
ACTUATOR POSITION DESIGNATIONAT EACH POLE
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
AUXILIARY SWITCH FUNCTION AND QUANTITYALARM 1
THREAD QUANTITY PER INCH32
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 2.5
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 416.0
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES MINIMUM 1.021 AND INCHES MAXIMUM 1.041
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES MINIMUM 2.740 AND INCHES MAXIMUM 2.760
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES MINIMUM 1.021 AND INCHES MAXIMUM 1.041
FRAGILITY FACTORMODERATELY RUGGED
BOSS HEIGHTINCHES MINIMUM 0.146 AND INCHES MAXIMUM 0.166
MOUNTING SURFACE TO TERMINAL END DISTANCEINCHES NOMINAL 3.239
POLE QUANTITY3
ARC QUENCHING METHODMAGNETIC BLOWOUT
MOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 6
INTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
BODY LENGTHINCHES MINIMUM 3.709 AND INCHES MAXIMUM 3.729
BODY WIDTHINCHES MINIMUM 3.042 AND INCHES MAXIMUM 3.062
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0
NOMINAL THREAD SIZEINCHES 0.138
RESET METHODMANUAL

MOE rules

MOE ruleMOE CDDate assignedPICAPICA LOAAuth collab
WG01WG01-OCT-17WG81WG
ZH01ZH01-APR-91ZH81ZH
ZJ01ZJ01-MAR-25ZJ81ZJ

Freight

ACTY CD
BD
NMFC
061700
NMFC sub
Z
Uniform freight class
34580
Less than truckload
W
Water commodity code
658
Type of cargo code
Z
Special handling code
9
Air dimension code
A
Air commodity code
HZ
NMF description
ELEC APPLIANCES/INSTRUMENTS NOI

Related items

Standardization

Item standardization code
2
Orig stdzn dec
TX
Dt stdzn dec
13-SEP-1968
NIIN status code
0

Request a quote

Your request goes to A-DEFENSE, a US Defense supplier in Texas, who will reply by email.