Catalog item

CIRCUIT BREAKER

5925FSC
00NCB code
797-9696Item number
NIIN 00-797-9696
Request a quote
DEMIL code
A

Identification

Item name code
00136
PINC
0000136
Criticality code
Y
II
M
DEMIL code
A
DEMIL integrity code
1
NIIN assigned
01-JAN-62
Precious metals indicator
A
ADP equipment code
0
Hazardous material indicator
P
Schedule B export code
8536200040

Part numbers

Part numberCAGECAGE statusRNCCRNVCDocument availability codeRNAACRNFCRNSC
ETN100830086
L3HARRIS MARITIME POWER & ENERGY SOLUTIONS, INC. DBA SPD ELECTRICAL SYSTEMS, INC.
A525TX3D
ETN100833097
I-T-E IMPERIAL CORP SUB OF GOULD INC
H596HD1B
5224167-453711
NAVAL SEA SYSTEMS COMMAND
A59ATXB
MILC1736181349
MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
A59ETX3B
AQBA5081349
MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
A59EHD3B
63860-182340
L3HARRIS TECHNOLOGIES, INC.
A596HD1B
1244C52G0889946
EATON CORPORATION DBA EATON INOAC
A525ZZ
63860-19Y580
L3HARRIS TECHNOLOGIES, INC.
A526HD
2903283-810001
NAVAIR AND NAVSEA MANAGED ORIGINAL DESIGN ACTIVITY DWG NOT MATERIAL/PARTS SUPPLIER
A32ATX

Characteristics

MOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 2
TRIP RELEASE METHODALL LOCATIONS THERMAL-MAGNETIC
CIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 2.625
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 5000.0 AND DC 2500.0
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 0.625
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES NOMINAL 2.938
BOSS HEIGHTINCHES NOMINAL 0.125
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 500.0 AND DC 250.0
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT115.0
RESET METHODMANUAL
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
THREAD QUANTITY PER INCH24
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 50.0 AND AMPERES DC 50.0
BODY WIDTHINCHES NOMINAL 3.344
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 1.125
CRITICALITY CODE JUSTIFICATIONFEAT
SPECIAL FEATURESWEAPON SYSTEMS CRITICAL ITEM
FREQUENCY IN HERTZ60.0
MATERIALCASE PLASTIC
THREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TERMINAL TYPE AND QUANTITYQUICK DISCONNECT, FEMALE 6
NOMINAL THREAD SIZEINCHES 0.216
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 20.000 AND MAXIMUM AT 200 PCT 90.000
TRIP RELEASE AMBIENT TEMP RATINGALL LOCATIONS CELSIUS NOMINAL 50.0
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE AND AT POLE THREE
BODY HEIGHTINCHES NOMINAL 3.375
BODY STYLE
BODY LENGTHINCHES NOMINAL 4.125
TRIP RELEASE CHARACTERISTICALL LOCATIONS INSTANTANEOUS AND TIME DELAY
POLE QUANTITY3
MANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1

MOE rules

MOE ruleMOE CDDate assignedPICAPICA LOAAuth collab
WP01WP01-JUN-07WP81WP
YB01YB01-APR-91YB81YB
ZC01ZC01-APR-91ZC81ZC
ZG01ZG01-APR-91ZG81ZG
ZH01ZH01-APR-91ZH81ZH
ZR01ZR01-JUL-97ZR81ZR
ZT01ZT01-APR-91ZT81ZT
ZW01ZW01-NOV-98ZW81ZW

Freight

ACTY CD
XX
NMFC
061700
NMFC sub
Z
Uniform freight class
34580
Less than truckload
W
Water commodity code
658
Type of cargo code
Z
Special handling code
9
Air dimension code
A
Air commodity code
HZ
NMF description
ELEC APPLIANCES/INSTRUMENTS NOI

Related items

Standardization

Item standardization code
3
Orig stdzn dec
TX
Dt stdzn dec
03-SEP-1997
NIIN status code
0

Cancelled and replaced NIINs

FSCCancelled NIINNIIN status codeEffective dateDEMIL code
59255925-01-261-5622702-JUL-2026A
59255925-01-113-2743502-JUL-2026A

Request a quote