Catalog item

CIRCUIT BREAKER

5925FSC
00NCB code
821-6552Item number
NIIN 00-821-6552
Request a quote
DEMIL code
A

Identification

Item name code
00136
PINC
0000136
Criticality code
X
II
0
DEMIL code
A
DEMIL integrity code
1
NIIN assigned
01-JAN-62
Precious metals indicator
A
Hazardous material indicator
P
Schedule B export code
8536200040
Last known source of supply
S9E

Part numbers

Part numberCAGECAGE statusRNCCRNVCDocument availability codeRNAACRNSC
MP93281640
SAFRAN POWER USA, LLC
A595ZZB
930-009-70581640
SAFRAN POWER USA, LLC
A32EZZ

Characteristics

CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES MINIMUM 0.735 AND INCHES MAXIMUM 0.765
THREAD QUANTITY PER INCH32
MOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MAXIMUM 2.218
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 7.5
MOUNTING FACILITY TYPE AND QUANTITYTHREADED BUSHING 3
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
ACTUATOR POSITION DESIGNATIONAT EACH POLE
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
INTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
NOMINAL THREAD SIZEINCHES 0.469
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 15.000 AND MAXIMUM AT 200 PCT 55.000
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDHERMETICALLY SEALED AND SHOCK RESISTANT AND VIBRATION RESISTANT
TRIP RELEASE AMBIENT TEMP RATINGALL LOCATIONS CELSIUS NOMINAL 25.0
UNPACKAGED UNIT WEIGHTGRAMS NOMINAL 150.0
FREQUENCY IN HERTZ400.0
TEST DATA DOCUMENTDRAWING (THIS IS THE BASIC GOVERNING DRAWING, SUCH AS A CONTRACTOR DRAWING, ORIGINAL EQUIPMENT MANUFACTURER DRAWING, ETC.; EXCLUDES ANY SPECIFICATION, STANDARD OR OTHER DOCUMENT THAT MAY BE REFERENCED IN A BASIC GOVERNING DRAWING) 76374-FT-12
THREAD SERIES DESIGNATORUNS
POLE QUANTITY3
BODY STYLE
BUSHING LENGTHINCHES MINIMUM 0.235 AND INCHES MAXIMUM 0.265
BODY LENGTHINCHES MAXIMUM 2.250
BODY WIDTHINCHES MINIMUM 1.203 AND INCHES MAXIMUM 1.233
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 120.0
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 1200.0
CIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MINIMUM 0.689 AND INCHES MAXIMUM 0.179
FRAGILITY FACTORMODERATELY RUGGED
RESET METHODMANUAL
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITYPUSH-PULL 3
ACTUATOR FUNCTIONTRIP-RESET
TRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT138.0
TERMINAL TYPE AND QUANTITYTAB W/SCREW 6
TRIP RELEASE METHODALL LOCATIONS THERMAL

MOE rules

MOE ruleMOE CDDate assignedPICAPICA LOAAuth collab
YA01YA01-JAN-02YA81YA
YW01YW01-APR-91YW81YW
ZH01ZH01-APR-91ZH81ZH
ZR01ZR01-JUL-97ZR81ZR
ZW01ZW01-NOV-05ZW81ZW

Freight

ACTY CD
XX
NMFC
061700
NMFC sub
Z
Uniform freight class
34580
Less than truckload
W
Water commodity code
658
Type of cargo code
Z
Special handling code
9
Air dimension code
A
Air commodity code
HZ
NMF description
ELEC APPLIANCES/INSTRUMENTS NOI

Related items

Standardization

Item standardization code
3
Orig stdzn dec
TX
Dt stdzn dec
17-MAR-1971
NIIN status code
0