Catalog item
Request a quoteCIRCUIT BREAKER
5925FSC
00NCB code
837-3663Item number
NIIN 00-837-3663
- DEMIL code
- A
Identification
- Item name code
- 00136
- PINC
- 0000136
- Criticality code
- X
- II
- 0
- DEMIL code
- A
- DEMIL integrity code
- 1
- NIIN assigned
- 01-JAN-62
- Precious metals indicator
- U
- Hazardous material indicator
- P
- Schedule B export code
- 8536200040
- Last known source of supply
- S9E
Part numbers
| Part number | CAGE | CAGE status | RNCC | RNVC | Document availability code | RNAAC | RNFC | RNSC |
|---|---|---|---|---|---|---|---|---|
| 3XAM1516MG3-65AMP120VACTDC3-400 | 74193 EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV | H | 5 | 9 | E | TX | 3 | D |
| 3XAM1516MG3-65AMP120VACTDC13 | 74193 EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV | H | 5 | 9 | E | TX | 3 | D |
| 9157025 | 18876 US ARMY AVIATION AND MISSILE COMMAND | A | 3 | 2 | A | TX | 3 | D |
Characteristics
| MOUNTING FACILITY TYPE AND QUANTITY | THREADED HOLE(S) 6 |
|---|---|
| FREQUENCY IN HERTZ | 400.0 |
| MATERIAL | CASE PLASTIC |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TERMINAL TYPE AND QUANTITY | THREADED STUD 6 |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | ALL LOCATIONS AC 120.0 |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | ALL LOCATIONS AC 2000.0 |
| CIRCUIT PROTECTION TYPE | ALL LOCATIONS OVERCURRENT |
| TRIP RELEASE METHOD | ALL LOCATIONS MAGNETIC-HYDRAULIC |
| TRIP RELEASE CHARACTERISTIC | ALL LOCATIONS TIME DELAY |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| POLE QUANTITY | 3 |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | INCHES NOMINAL 2.750 |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | INCHES NOMINAL 1.031 |
| BOSS HEIGHT | INCHES NOMINAL 0.156 |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | INCHES NOMINAL 3.359 |
| BODY STYLE | |
| BODY LENGTH | INCHES NOMINAL 3.719 |
| BODY WIDTH | INCHES NOMINAL 3.052 |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES NOMINAL 3.063 |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | INCHES NOMINAL 1.031 |
| NOMINAL THREAD SIZE | INCHES 0.138 |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | ALL LOCATIONS MINIMUM AT 200 PCT 0.300 AND MAXIMUM AT 200 PCT 1.000 AND MINIMUM AT 300 PCT 0.100 AND MAXIMUM AT 300 PCT 0.300 AND MINIMUM AT 400 PCT 0.040 AND MAXIMUM AT 400 PCT 0.150 |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT AND EXPLOSION RESISTANT |
| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
| INTERNAL TRIP RELEASE CONFIGURATION | ALL LOCATIONS SERIES TRIP |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | ALL LOCATIONS AMPERES AC 65.0 |
| ULTIMATE TRIP TIME PER POLE IN SECONDS | ALL LOCATIONS MINIMUM 0.800 AND MAXIMUM 3.000 |
| RESET METHOD | MANUAL |
| THREAD QUANTITY PER INCH | 32 |
| MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 3 |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MOE rules
| MOE rule | MOE CD | Date assigned | PICA | PICA LOA | Auth collab |
|---|---|---|---|---|---|
| YB01 | YB | 01-SEP-08 | YB | 81 | YB |
| ZR01 | ZR | 01-DEC-07 | ZR | 81 | ZR |
Freight
- ACTY CD
- XX
- NMFC
- 061700
- NMFC sub
- Z
- Uniform freight class
- 34580
- Less than truckload
- W
- Water commodity code
- 658
- Type of cargo code
- Z
- Special handling code
- 9
- Air dimension code
- A
- Air commodity code
- HZ
- NMF description
- ELEC APPLIANCES/INSTRUMENTS NOI
Related items
Standardization
- Item standardization code
- 2
- Orig stdzn dec
- TX
- Dt stdzn dec
- 10-MAY-1971
- NIIN status code
- 0
Request a quote
Your request goes to A-DEFENSE, a US Defense supplier in Texas, who will reply by email.