Catalog item

CIRCUIT BREAKER

5925FSC
00NCB code
875-0221Item number
NIIN 00-875-0221
Request a quote
DEMIL code
A

Identification

Item name code
00136
PINC
0000136
Criticality code
X
II
0
DEMIL code
A
DEMIL integrity code
1
NIIN assigned
03-NOV-67
Precious metals indicator
A
Hazardous material indicator
P
Schedule B export code
8536200040
Last known source of supply
S9E

Part numbers

Part numberCAGECAGE statusRNCCRNVCDocument availability codeRNAACRNFCRNSC
SM333-3-5-230VAC400C174193
EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
H59ETX3B
79-146-2574193
EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
H39ATX3D
788C689H2597942
NORTHROP GRUMMAN SYSTEMS CORPORATION DBA NORTHROP GRUMMAN SYSTEMS CORP
A72ATX3D

Characteristics

INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND EXPLOSION RESISTANT AND HERMETICALLY SEALED
FREQUENCY IN HERTZ400.0
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 1.000 AND MAXIMUM AT 200 PCT 13.000
INTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
NOMINAL THREAD SIZEINCHES 0.375
MANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO
BODY STYLE
BUSHING LENGTHINCHES NOMINAL 0.375
BODY LENGTHINCHES MAXIMUM 1.500
RESET METHODMANUAL
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
TRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
ULTIMATE TRIP TIME PER POLE IN SECONDSALL LOCATIONS MINIMUM 8.000 AND MAXIMUM 15.500
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 230.0
POLE QUANTITY3
ARC QUENCHING METHODMAGNETIC BLOWOUT
MOUNTING FACILITY TYPE AND QUANTITYTHREADED BUSHING WITH PANEL SEAL 1
TERMINAL TYPE AND QUANTITYWIRE HOOK 6
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SPECIAL HANDLING FEATUREMAGNETIC
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 300.0
CIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
THREAD QUANTITY PER INCH32
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 3.5
BODY WIDTHINCHES MAXIMUM 1.875
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 0.875
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 0.625
FRAGILITY FACTORMODERATELY RUGGED
MOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MAXIMUM 1.780
TEST DATA DOCUMENTDRAWING (THIS IS THE BASIC GOVERNING DRAWING, SUCH AS A CONTRACTOR DRAWING, ORIGINAL EQUIPMENT MANUFACTURER DRAWING, ETC.; EXCLUDES ANY SPECIFICATION, STANDARD OR OTHER DOCUMENT THAT MAY BE REFERENCED IN A BASIC GOVERNING DRAWING) 97942-788C689H25
THREAD SERIES DESIGNATORUNEF
TRIP RELEASE METHODALL LOCATIONS MAGNETIC-HYDRAULIC

MOE rules

MOE ruleMOE CDDate assignedPICAPICA LOAAuth collab
YB01YB01-APR-91YB81YB
ZU01ZU01-APR-91ZU81ZU

Freight

ACTY CD
TX
NMFC
061700
NMFC sub
Z
Uniform freight class
34580
Less than truckload
W
Water commodity code
658
Type of cargo code
Z
Special handling code
9
Air dimension code
A
Air commodity code
HZ
NMF description
ELEC APPLIANCES/INSTRUMENTS NOI

Related items

Standardization

Item standardization code
2
Orig stdzn dec
TX
Dt stdzn dec
15-DEC-1974
NIIN status code
0

Request a quote

Your request goes to A-DEFENSE, a US Defense supplier in Texas, who will reply by email.