Catalog item

CIRCUIT BREAKER

5925FSC
00NCB code
877-2862Item number
NIIN 00-877-2862
Request a quote
DEMIL code
A

Identification

Item name code
00136
PINC
0000136
Criticality code
X
II
0
DEMIL code
A
DEMIL integrity code
1
NIIN assigned
01-JAN-62
Precious metals indicator
U
Hazardous material indicator
P
Schedule B export code
8536200040
Last known source of supply
SMS

Part numbers

Part numberCAGECAGE statusRNCCRNVCDocument availability codeRNAACRNFCRNSC
53-119-3-MG374193
EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
H595TXB
53-119MG3-30-416VAC400C374193
EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
H59ETX3B
53-119-MG3-3L3330
HEINEMANN ELECTRIC CANADA INCDIVISION OF EATON CORP
A5269Z4D
9176489-118876
US ARMY AVIATION AND MISSILE COMMAND
A32ATX3D

Characteristics

MANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 3
INTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
NOMINAL THREAD SIZEINCHES 0.138
BODY STYLE
BODY LENGTHINCHES NOMINAL 3.719
BODY WIDTHINCHES NOMINAL 3.062
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 3.062
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLE
POLE QUANTITY3
MOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 6
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
THREAD QUANTITY PER INCH32
TRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0
RESET METHODMANUAL
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 500.0
CIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
TRIP RELEASE METHODALL LOCATIONS MAGNETIC-HYDRAULIC
MATERIALCASE PLASTIC
THREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 1.031
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 2.750
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES NOMINAL 1.031
BOSS HEIGHTINCHES NOMINAL 0.156
MOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MAXIMUM 3.310
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 416.0
TERMINAL TYPE AND QUANTITYTHREADED STUD 6
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 0.300 AND MAXIMUM AT 200 PCT 0.950
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND MOISTURE RESISTANT
FREQUENCY IN HERTZ400.0
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 30.0

MOE rules

MOE ruleMOE CDDate assignedPICAPICA LOAAuth collab
WG01WG01-OCT-17WG81WG
YB01YB01-AUG-95YB81YB
YD01YD01-AUG-16YD81YD
YJ01YJ01-APR-91YJ81YJ
ZH01ZH01-APR-91ZH81ZH
ZS01ZS01-APR-91ZS81ZS
ZU01ZU01-AUG-95ZU81ZU
ZW01ZW01-NOV-05ZW81ZW
VJ01VJ01-DEC-18VJ81VJ

Freight

ACTY CD
XX
NMFC
061700
NMFC sub
Z
Uniform freight class
34580
Less than truckload
W
Water commodity code
72D
Type of cargo code
Z
Special handling code
9
Air dimension code
A
Air commodity code
HZ
NMF description
ELEC APPLIANCES/INSTRUMENTS NOI

Related items

Standardization

Item standardization code
2
Orig stdzn dec
TX
Dt stdzn dec
17-JUL-1970
NIIN status code
0

Request a quote