Catalog item

CIRCUIT BREAKER

5925FSC
01NCB code
072-9186Item number
NIIN 01-072-9186
Request a quote
DEMIL code
A

Identification

Item name code
00136
PINC
0000136
Criticality code
X
II
0
DEMIL code
A
DEMIL integrity code
1
NIIN assigned
06-MAR-79
Precious metals indicator
U
Hazardous material indicator
P
Schedule B export code
8536200040

Part numbers

Part numberCAGECAGE statusRNCCRNVCDocument availability codeRNAACRNFCRNSC
898668-23B150
RAYTHEON COMPANY DBA RAYTHEON CO
A3249Z
898668-249956
RAYTHEON COMPANY DIV CORP
A5949Z4B
CD3-Z247-274193
EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
H59ETXB

Characteristics

BODY STYLE
MOUNTING SLOT WIDTHINCHES NOMINAL 0.164
BODY LENGTHINCHES NOMINAL 5.844
BODY WIDTHINCHES NOMINAL 3.096
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 3.546
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 1.032
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 2.750
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES NOMINAL 1.032
FRAGILITY FACTORMODERATELY RUGGED
BOSS HEIGHTINCHES NOMINAL 0.218
MOUNTING SURFACE TO TERMINAL END DISTANCEINCHES NOMINAL 2.609
POLE QUANTITY3
ARC QUENCHING METHODMAGNETIC BLOWOUT
MOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 6 AND SLOT 6
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SPECIAL HANDLING FEATUREMAGNETIC
THREAD QUANTITY PER INCH32
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 25.0
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 480.0
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 5000.0
CIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
TRIP RELEASE METHODALL LOCATIONS MAGNETIC-HYDRAULIC
TRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
RESET METHODMANUAL
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 3
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLE
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
INTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
NOMINAL THREAD SIZEINCHES 0.138
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 5.000 AND MAXIMUM AT 200 PCT 20.000
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF
FREQUENCY IN HERTZ60.0
MATERIALCASE PLASTIC
THREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TERMINAL TYPE AND QUANTITYTHREADED STUD 6

MOE rules

MOE rule
ZG01
MOE CD
ZG
Date assigned
01-APR-91
PICA
ZG
PICA LOA
81
Auth collab
ZG

Freight

ACTY CD
ZN
NMFC
061700
NMFC sub
Z
Uniform freight class
34580
Less than truckload
W
Less than carload
P
Water commodity code
658
Type of cargo code
Z
Special handling code
9
Air dimension code
A
Air commodity code
HZ
NMF description
ELEC APPLIANCES/INSTRUMENTS NOI

Related items

Standardization

Item standardization code
5
Orig stdzn dec
97
Dt stdzn dec
06-MAR-1979
NIIN status code
0

Request a quote