Catalog item
Request a quoteCIRCUIT BREAKER
5925FSC
01NCB code
083-4816Item number
NIIN 01-083-4816
- DEMIL code
- A
Identification
- Item name code
- 00136
- PINC
- 0000136
- Criticality code
- X
- II
- 0
- DEMIL code
- A
- DEMIL integrity code
- 1
- NIIN assigned
- 24-SEP-79
- Precious metals indicator
- A
- Hazardous material indicator
- P
- Schedule B export code
- 8536200040
- Last known source of supply
- S9E
Part numbers
Characteristics
| BODY STYLE | |
|---|---|
| BODY LENGTH | INCHES NOMINAL 2.490 |
| BODY WIDTH | INCHES MAXIMUM 2.265 |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES NOMINAL 1.940 |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | INCHES NOMINAL 0.750 |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | INCHES NOMINAL 2.060 |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | INCHES NOMINAL 0.750 |
| BOSS HEIGHT | INCHES NOMINAL 0.150 |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | INCHES MAXIMUM 2.491 |
| POLE QUANTITY | 4 |
| MOUNTING FACILITY TYPE AND QUANTITY | THREADED HOLE(S) 8 |
| THREAD QUANTITY PER INCH | 32 |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | SECOND LOCATION AMPERES AC 10.0 |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | THIRD LOCATION AMPERES AC 10.0 |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | FIRST LOCATION AMPERES AC 10.0 |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | SECOND LOCATION AC 250.0 |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | THIRD LOCATION AC 250.0 |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | FOURTH LOCATION DC 28.0 |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | FIRST LOCATION AC 250.0 |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | FOURTH LOCATION DC 2000.0 |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | THIRD LOCATION AC 5000.0 |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | FIRST LOCATION AC 5000.0 |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | SECOND LOCATION AC 5000.0 |
| CIRCUIT PROTECTION TYPE | FIRST LOCATION OVERCURRENT |
| CIRCUIT PROTECTION TYPE | SECOND LOCATION OVERCURRENT |
| CIRCUIT PROTECTION TYPE | FOURTH LOCATION UNDERVOLTAGE |
| CIRCUIT PROTECTION TYPE | THIRD LOCATION OVERCURRENT |
| TRIP RELEASE METHOD | ALL LOCATIONS MAGNETIC |
| TRIP RELEASE CHARACTERISTIC | FIRST LOCATION TIME DELAY |
| TRIP RELEASE CHARACTERISTIC | SECOND LOCATION TIME DELAY |
| TRIP RELEASE CHARACTERISTIC | FOURTH LOCATION INSTANTANEOUS |
| TRIP RELEASE CHARACTERISTIC | THIRD LOCATION TIME DELAY |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 |
| RESET METHOD | MANUAL |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 4 |
| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, THREE, AND FOUR LINKED |
| INTERNAL TRIP RELEASE CONFIGURATION | ALL LOCATIONS SERIES TRIP |
| NOMINAL THREAD SIZE | INCHES 0.138 |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | SECOND LOCATION NOMINAL AT 200 PCT 0.990 |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | FIRST LOCATION NOMINAL AT 200 PCT 0.990 |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | THIRD LOCATION NOMINAL AT 200 PCT 0.990 |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | CORROSION RESISTANT AND MOISTURE RESISTANT |
| FREQUENCY IN HERTZ | 60.0 |
| MATERIAL | CASE PLASTIC |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TERMINAL TYPE AND QUANTITY | THREADED STUD 8 |
MOE rules
- MOE rule
- ZC01
- MOE CD
- ZC
- Date assigned
- 01-APR-91
- PICA
- ZC
- PICA LOA
- 81
- Auth collab
- ZC
Freight
- ACTY CD
- TX
- NMFC
- 061700
- NMFC sub
- Z
- Uniform freight class
- 34580
- Less than truckload
- W
- Water commodity code
- 658
- Type of cargo code
- Z
- Special handling code
- 9
- Air dimension code
- A
- Air commodity code
- HZ
- NMF description
- ELEC APPLIANCES/INSTRUMENTS NOI
Related items
Standardization
- Item standardization code
- 2
- Orig stdzn dec
- TX
- Dt stdzn dec
- 16-MAY-1980
- NIIN status code
- 0
Request a quote