Catalog item

CIRCUIT BREAKER

5925FSC
01NCB code
202-0131Item number
NIIN 01-202-0131
Request a quote
DEMIL code
A

Identification

Item name code
00136
PINC
0000136
Criticality code
X
II
0
DEMIL code
A
DEMIL integrity code
1
NIIN assigned
27-FEB-85
Precious metals indicator
U
Hazardous material indicator
P
Schedule B export code
8536200040

Part numbers

Part number
JA2S-A8-BB-04-W
CAGE
74193
EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
CAGE status
H
RNCC
3
RNVC
9
Document availability code
E
RNAAC
TX
RNSC
D

Characteristics

BODY STYLE
BUSHING LENGTHINCHES NOMINAL 0.130
BODY LENGTHINCHES NOMINAL 2.000
BODY WIDTHINCHES NOMINAL 1.500
BODY HEIGHTINCHES NOMINAL 1.930
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 1.560
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 0.750
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 1.660
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES NOMINAL 0.750
FRAGILITY FACTORMODERATELY RUGGED
POLE QUANTITY2
ARC QUENCHING METHODMAGNETIC BLOWOUT
MOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 4
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SPECIAL HANDLING FEATUREMAGNETIC
THREAD QUANTITY PER INCH32
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 10.0
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 250.0
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 1000.0
CIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
TRIP RELEASE METHODALL LOCATIONS MAGNETIC-HYDRAULIC
TRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
RESET METHODMANUAL
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
INTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
NOMINAL THREAD SIZEMILLIMETERS 3.0
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 2.500 AND MAXIMUM AT 200 PCT 20.000
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND MOISTURE RESISTANT
UNPACKAGED UNIT WEIGHTOUNCES NOMINAL 5.000
FREQUENCY IN HERTZ50.0 OR 60.0
MATERIALCASE PLASTIC
THREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TERMINAL TYPE AND QUANTITYTAB, SOLDER LUG 4

MOE rules

MOE ruleMOE CDDate assignedPICAPICA LOAAuth collab
ZG01ZG01-APR-91ZG81ZG
ZR01ZR01-APR-91ZR81ZR

Freight

ACTY CD
ZG

Related items

Standardization

Item standardization code
5
Orig stdzn dec
97
Dt stdzn dec
27-FEB-1985
NIIN status code
0

Request a quote

Your request goes to A-DEFENSE, a US Defense supplier in Texas, who will reply by email.