Catalog item
Request a quoteCIRCUIT BREAKER
5925FSC
01NCB code
219-5983Item number
NIIN 01-219-5983
- DEMIL code
- A
Identification
- Item name code
- 00136
- PINC
- 0000136
- Criticality code
- X
- II
- 0
- DEMIL code
- A
- DEMIL integrity code
- 1
- NIIN assigned
- 30-OCT-85
- Precious metals indicator
- U
- Hazardous material indicator
- P
- Schedule B export code
- 8536200040
Part numbers
- Part number
- 205-111-1REC5-62F5-203
- CAGE
- 81541SENSATA TECHNOLOGIES MARYLAND, INC
- CAGE status
- A
- RNCC
- 3
- RNVC
- 2
- Document availability code
- 4
- RNAAC
- 9Z
- RNSC
- A
Characteristics
| BODY STYLE | |
|---|---|
| BODY LENGTH | INCHES NOMINAL 2.490 |
| BODY WIDTH | INCHES MAXIMUM 2.265 |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES NOMINAL 1.940 |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | INCHES NOMINAL 0.750 |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | INCHES NOMINAL 2.060 |
| SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | INCHES NOMINAL 0.750 |
| FRAGILITY FACTOR | MODERATELY RUGGED |
| BOSS HEIGHT | INCHES NOMINAL 0.150 |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | INCHES NOMINAL 2.475 |
| POLE QUANTITY | 3 |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| MOUNTING FACILITY TYPE AND QUANTITY | THREADED HOLE(S) 6 |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| FEATURES PROVIDED | HIGH INRUSH PROTECTION |
| THREAD QUANTITY PER INCH | 32 |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | ALL LOCATIONS AMPERES AC 20.0 |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | ALL LOCATIONS AC 480.0 |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | ALL LOCATIONS AC 5000.0 |
| CIRCUIT PROTECTION TYPE | ALL LOCATIONS OVERCURRENT |
| TRIP RELEASE METHOD | ALL LOCATIONS MAGNETIC |
| TRIP RELEASE CHARACTERISTIC | ALL LOCATIONS TIME DELAY |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 |
| RESET METHOD | MANUAL |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 3 |
| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
| AUXILIARY SWITCH FUNCTION AND QUANTITY | ALARM 1 |
| INTERNAL TRIP RELEASE CONFIGURATION | ALL LOCATIONS SERIES TRIP |
| NOMINAL THREAD SIZE | INCHES 0.138 |
| SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE THREE |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | ALL LOCATIONS MINIMUM AT 200 PCT 2.200 AND MAXIMUM AT 200 PCT 20.000 |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
| SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
| SWITCH CURRENT RATING AND TYPE IN AMPS | AC 10.0 AND DC 3.0 |
| SWITCH VOLTAGE RATING AND TYPE IN VOLTS | AC 250.0 AND DC 50.0 |
| UNPACKAGED UNIT WEIGHT | OUNCES NOMINAL 9.500 |
| FREQUENCY IN HERTZ | 50.0 OR 60.0 |
| MATERIAL | CASE PLASTIC |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TERMINAL TYPE AND QUANTITY | THREADED STUD 6 |
MOE rules
- MOE rule
- ZK01
- MOE CD
- ZK
- Date assigned
- 01-FEB-96
- PICA
- ZK
- PICA LOA
- 81
- Auth collab
- ZK
Freight
- ACTY CD
- ZK
Related items
Standardization
- Item standardization code
- 5
- Orig stdzn dec
- 97
- Dt stdzn dec
- 30-OCT-1985
- NIIN status code
- 0
Request a quote
Your request goes to A-DEFENSE, a US Defense supplier in Texas, who will reply by email.