Catalog item

CIRCUIT BREAKER

5925FSC
01NCB code
225-3430Item number
NIIN 01-225-3430
Request a quote
DEMIL code
A

Identification

Item name code
00136
PINC
0000136
Criticality code
X
II
0
DEMIL code
A
DEMIL integrity code
1
NIIN assigned
31-JAN-86
Precious metals indicator
A
Hazardous material indicator
P
Schedule B export code
8536200040
Last known source of supply
ZNC

Part numbers

Part numberCAGECAGE statusRNCCRNVCDocument availability codeRNAAC
UPL-11-1-66-10381541
SENSATA TECHNOLOGIES MARYLAND, INC
A32ETX
2854168-496214
RAYTHEON COMPANY DBA RAYTHEON
A525TX
S90-0017-00114304
L3HARRIS TECHNOLOGIES, INC. DBA HARRIS CORP DIV HARRIS DEFENSE COMMUNICATIONS
A526TX

Characteristics

BODY STYLE
BODY LENGTHINCHES MINIMUM 2.480 AND INCHES MAXIMUM 2.500
BODY WIDTHINCHES MAXIMUM 1.515
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MINIMUM 1.925 AND INCHES MAXIMUM 1.955
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES MINIMUM 0.735 AND INCHES MAXIMUM 0.765
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES MINIMUM 2.050 AND INCHES MAXIMUM 2.070
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES MINIMUM 0.735 AND INCHES MAXIMUM 0.765
FRAGILITY FACTORMODERATELY RUGGED
BOSS HEIGHTINCHES MINIMUM 0.135 AND INCHES MAXIMUM 0.165
MOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MAXIMUM 2.490
POLE QUANTITY2
ARC QUENCHING METHODMAGNETIC BLOWOUT
MOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 4
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SPECIAL HANDLING FEATUREMAGNETIC
THREAD QUANTITY PER INCH32
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 10.0
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 250.0
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 1000.0
CIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
TRIP RELEASE METHODALL LOCATIONS MAGNETIC
TRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
RESET METHODMANUAL
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 2
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLE
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE AND TWO LINKED
INTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
NOMINAL THREAD SIZEINCHES 0.138
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 10.000 AND MAXIMUM AT 200 PCT 100.000
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDMOISTURE RESISTANT AND SALT SPRAY PROOF AND SHOCK RESISTANT AND VIBRATION RESISTANT
UNPACKAGED UNIT WEIGHTOUNCES NOMINAL 7.400
FREQUENCY IN HERTZ50.0 OR 60.0
MATERIALCASE PLASTIC
THREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TERMINAL TYPE AND QUANTITYTHREADED STUD 4

MOE rules

MOE ruleMOE CDDate assignedPICAPICA LOAAuth collab
YB01YB01-JUN-99YB81YB
ZE01ZE01-APR-91ZE81ZE
ZW01ZW01-NOV-98ZW81ZW

Freight

ACTY CD
TH

Related items

Standardization

Item standardization code
5
Orig stdzn dec
97
Dt stdzn dec
31-JAN-1986
NIIN status code
0

Request a quote