Catalog item
Request a quoteCIRCUIT BREAKER
5925FSC
01NCB code
237-6865Item number
NIIN 01-237-6865
- DEMIL code
- A
Identification
- Item name code
- 00136
- PINC
- 0000136
- Criticality code
- X
- II
- 0
- DEMIL code
- A
- DEMIL integrity code
- 1
- NIIN assigned
- 05-AUG-86
- Precious metals indicator
- A
- ADP equipment code
- 0
- Hazardous material indicator
- P
- Schedule B export code
- 8536200040
- Last known source of supply
- S9E
Part numbers
| Part number | CAGE | CAGE status | RNCC | RNVC | Document availability code | RNAAC | RNSC |
|---|---|---|---|---|---|---|---|
| MIL-C-39019/5 | 81349 MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M | A | 4 | 1 | 4 | 9Z | D |
| M39019-5-49 | 81349 MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M | A | 5 | 9 | 4 | 9Z | B |
| M39019/5-230 | 81349 MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M | A | 2 | 2 | 4 | 9Z | D |
Characteristics
| BODY STYLE | |
|---|---|
| BUSHING LENGTH | INCHES MINIMUM 0.332 AND INCHES MAXIMUM 0.380 |
| BODY LENGTH | INCHES MAXIMUM 1.937 |
| BODY WIDTH | INCHES MAXIMUM 1.562 |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES MAXIMUM 0.906 |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | INCHES MAXIMUM 1.828 |
| POLE QUANTITY | 3 |
| MOUNTING FACILITY TYPE AND QUANTITY | THREADED BUSHING 1 |
| THREAD QUANTITY PER INCH | 32 |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | ALL LOCATIONS AMPERES AC 5.0 AND AMPERES DC 5.0 |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | ALL LOCATIONS AC 240.0 AND DC 50.0 |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | ALL LOCATIONS AC 300.0 AND DC 500.0 |
| CIRCUIT PROTECTION TYPE | ALL LOCATIONS OVERCURRENT |
| TRIP RELEASE METHOD | ALL LOCATIONS MAGNETIC |
| TRIP RELEASE CHARACTERISTIC | ALL LOCATIONS TIME DELAY |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 200.0 |
| ULTIMATE TRIP TIME PER POLE IN SECONDS | ALL LOCATIONS MAXIMUM 0.950 |
| RESET METHOD | MANUAL |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| INTERNAL TRIP RELEASE CONFIGURATION | ALL LOCATIONS SERIES TRIP |
| NOMINAL THREAD SIZE | INCHES 0.375 |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | ALL LOCATIONS MINIMUM AT 200 PCT 0.055 AND MAXIMUM AT 200 PCT 0.950 |
| FREQUENCY IN HERTZ | 60.0 OR 400.0 |
| TEST DATA DOCUMENT | SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). 81349--IL-C-39019 |
| THREAD SERIES DESIGNATOR | UNEF |
| TERMINAL TYPE AND QUANTITY | WIRE HOOK 2 |
| SPECIFICATION/STANDARD DATA | GOVERNMENT SPECIFICATION 81349--IL-C-81349 TO 5 |
MOE rules
| MOE rule | MOE CD | Date assigned | PICA | PICA LOA | Auth collab |
|---|---|---|---|---|---|
| YB01 | YB | 01-JUN-99 | YB | 81 | YB |
| ZG01 | ZG | 01-NOV-11 | ZG | 81 | ZG |
| ZK01 | ZK | 01-JUL-00 | ZK | 81 | ZK |
Freight
- ACTY CD
- ZG
Related items
Standardization
- Item standardization code
- E
- Orig stdzn dec
- TX
- Dt stdzn dec
- 30-AUG-1989
- NIIN status code
- 0
Request a quote
Your request goes to A-DEFENSE, a US Defense supplier in Texas, who will reply by email.