Catalog item
Request a quoteCIRCUIT BREAKER
5925FSC
01NCB code
263-9150Item number
NIIN 01-263-9150
- DEMIL code
- A
Identification
- Item name code
- 00136
- PINC
- 0000136
- Criticality code
- X
- II
- 0
- DEMIL code
- A
- DEMIL integrity code
- 1
- NIIN assigned
- 22-SEP-87
- Precious metals indicator
- U
- Hazardous material indicator
- P
- Schedule B export code
- 8536200040
Part numbers
| Part number | CAGE | CAGE status | RNCC | RNVC | Document availability code | RNAAC | RNFC | RNSC |
|---|---|---|---|---|---|---|---|---|
| JA3S-T38-DB-04-W-6.5A/415V/253 | 74193 EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV | H | 3 | 9 | E | TX | D | |
| 42141-346-00-9 | K4556 BRITISH AEROSPACE DEFENCE SYSTEMS LTD T/A BAE SYSTEMS | R | 5 | 9 | 2 | ZK | 4 | B |
| 42141-346-00-9 | KC1M9 BAE SYSTEMS MARITIME SERVICES LIMITED | A | 5 | 2 | 5 | ZK | D |
Characteristics
| BODY STYLE | |
|---|---|
| BODY LENGTH | INCHES MINIMUM 1.985 AND INCHES MAXIMUM 2.015 |
| BODY WIDTH | INCHES MINIMUM 2.245 AND INCHES MAXIMUM 2.255 |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES MINIMUM 1.555 AND INCHES MAXIMUM 1.565 |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | INCHES MINIMUM 0.745 AND INCHES MAXIMUM 0.755 |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | INCHES MINIMUM 1.655 AND INCHES MAXIMUM 1.665 |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | INCHES MINIMUM 0.745 AND INCHES MAXIMUM 0.755 |
| FRAGILITY FACTOR | MODERATELY RUGGED |
| BOSS HEIGHT | INCHES MINIMUM 0.125 AND INCHES MAXIMUM 0.135 |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | INCHES MINIMUM 1.835 AND INCHES MAXIMUM 1.845 |
| POLE QUANTITY | 3 |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| MOUNTING FACILITY TYPE AND QUANTITY | THREADED HOLE(S) 6 |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| THREAD QUANTITY PER INCH | 32 |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | ALL LOCATIONS AMPERES AC 6.5 |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | ALL LOCATIONS AC 415.0 |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | ALL LOCATIONS AC 1000.0 |
| CIRCUIT PROTECTION TYPE | ALL LOCATIONS OVERCURRENT |
| TRIP RELEASE METHOD | ALL LOCATIONS MAGNETIC-HYDRAULIC |
| TRIP RELEASE CHARACTERISTIC | ALL LOCATIONS TIME DELAY |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 |
| RESET METHOD | MANUAL |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 3 |
| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
| INTERNAL TRIP RELEASE CONFIGURATION | ALL LOCATIONS SERIES TRIP |
| NOMINAL THREAD SIZE | INCHES 0.138 |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | ALL LOCATIONS MINIMUM AT 200 PCT 2.000 AND MAXIMUM AT 200 PCT 20.000 |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
| FREQUENCY IN HERTZ | 50.0 OR 60.0 |
| MATERIAL | CASE PLASTIC |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TERMINAL TYPE AND QUANTITY | TAB, SOLDER LUG 6 |
MOE rules
- MOE rule
- ZK01
- MOE CD
- ZK
- Date assigned
- 01-APR-91
- PICA
- ZK
- PICA LOA
- 81
- Auth collab
- ZK
Freight
- ACTY CD
- ZK
Related items
Standardization
- Item standardization code
- 5
- Orig stdzn dec
- 97
- Dt stdzn dec
- 22-SEP-1987
- NIIN status code
- 0
Request a quote