Catalog item

CIRCUIT BREAKER

5925FSC
01NCB code
307-0691Item number
NIIN 01-307-0691
Request a quote
DEMIL code
A

Identification

Item name code
00136
PINC
0000136
Criticality code
X
II
0
DEMIL code
A
DEMIL integrity code
1
NIIN assigned
07-SEP-89
Precious metals indicator
U
Hazardous material indicator
P
Schedule B export code
8536200040

Part numbers

Part numberCAGECAGE statusRNCCRNVCDocument availability codeRNAACRNFCRNSC
APL-111-1REC2-42-153-MA81541
SENSATA TECHNOLOGIES MARYLAND, INC
A32ETX
91501174F6481
THALES SA
A524ZF4B

Characteristics

BODY STYLE
BODY LENGTHINCHES MINIMUM 2.480 AND INCHES MAXIMUM 2.500
BODY WIDTHINCHES MAXIMUM 2.250
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 1.940
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 0.750
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES MINIMUM 2.050 AND INCHES MAXIMUM 2.070
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES NOMINAL 0.750
FRAGILITY FACTORMODERATELY RUGGED
BOSS HEIGHTINCHES NOMINAL 0.150
MOUNTING SURFACE TO TERMINAL END DISTANCEINCHES NOMINAL 2.475
POLE QUANTITY3
ARC QUENCHING METHODMAGNETIC BLOWOUT
MOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 6
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SPECIAL HANDLING FEATUREMAGNETIC
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 15.0
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 250.0
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 5000.0
CIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
TRIP RELEASE METHODALL LOCATIONS MAGNETIC
TRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT115.0
RESET METHODMANUAL
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 3
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLE
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
AUXILIARY SWITCH FUNCTION AND QUANTITYALARM 1
INTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
NOMINAL THREAD SIZEMILLIMETERS 3.0
THREAD PITCH IN MILLIMETERS0.50
SWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE ONE
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 2.000 AND MAXIMUM AT 200 PCT 22.000
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND MOISTURE RESISTANT AND SALT SPRAY PROOF AND SHOCK RESISTANT AND VIBRATION RESISTANT
SWITCH TERMINAL TYPEQUICK DISCONNECT, MALE
SWITCH CURRENT RATING AND TYPE IN AMPSAC 10.0 AND DC 3.0
SWITCH VOLTAGE RATING AND TYPE IN VOLTSAC 250.0 AND DC 50.0
UNPACKAGED UNIT WEIGHTOUNCES NOMINAL 11.100
FREQUENCY IN HERTZ400.0
MATERIALCASE PLASTIC
THREAD SERIES DESIGNATORISO S
TERMINAL TYPE AND QUANTITYTHREADED STUD 6

MOE rules

MOE rule
ZF01
MOE CD
ZF
Date assigned
01-APR-91
PICA
ZF
PICA LOA
81
Auth collab
ZF

Freight

ACTY CD
ZF

Related items

Standardization

Item standardization code
5
Orig stdzn dec
97
Dt stdzn dec
07-SEP-1989
NIIN status code
0

Request a quote

Your request goes to A-DEFENSE, a US Defense supplier in Texas, who will reply by email.