Catalog item

CIRCUIT BREAKER

5925FSC
01NCB code
317-9964Item number
NIIN 01-317-9964
Request a quote
DEMIL code
A

Identification

Item name code
00136
PINC
0000136
Criticality code
X
II
0
DEMIL code
A
DEMIL integrity code
1
NIIN assigned
11-APR-90
Precious metals indicator
U
Hazardous material indicator
P
Schedule B export code
8536200040

Part numbers

Part numberCAGECAGE statusRNCCRNVCDocument availability codeRNAACRNFCRNSC
APGN-11-1REC4-66-10281541
SENSATA TECHNOLOGIES MARYLAND, INC
A32ETX
0219494G00F0555
MBDA FRANCE
A529ZF4B

Characteristics

THREAD PITCH DIAMETERSINCHES 0.4752 TO 0.4787
BODY STYLE
BUSHING LENGTHINCHES NOMINAL 0.625
BODY LENGTHINCHES NOMINAL 2.000
BODY WIDTHINCHES NOMINAL 1.500
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 1.530
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 0.750
NONTURN DEVICE RADIUSINCHES NOMINAL 0.656
NONTURN DEVICE LENGTHINCHES NOMINAL 0.130
NONTURN DEVICE DIAMETERINCHES MINIMUM 0.151 AND INCHES MAXIMUM 0.161
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
FRAGILITY FACTORMODERATELY RUGGED
MOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MAXIMUM 2.200
POLE QUANTITY2
ARC QUENCHING METHODMAGNETIC BLOWOUT
MOUNTING FACILITY TYPE AND QUANTITYTHREADED BUSHING WITH PANEL SEAL 1
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SPECIAL HANDLING FEATUREMAGNETIC
THREAD QUANTITY PER INCH32
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 1.0
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 250.0
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 3500.0
CIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
TRIP RELEASE METHODALL LOCATIONS MAGNETIC-HYDRAULIC
TRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT115.0
RESET METHODMANUAL
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO
AUXILIARY SWITCH FUNCTION AND QUANTITYALARM 1
INTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
NOMINAL THREAD SIZEINCHES 0.500
SWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE ONE
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 125 PCT 50.000 AND MAXIMUM AT 125 PCT 700.000 AND MINIMUM AT 150 PCT 30.000 AND MAXIMUM AT 150 PCT 400.000 AND MINIMUM AT 200 PCT 10.000 AND MAXIMUM AT 200 PCT 150.000 AND MINIMUM AT 400 PCT 1.500 AND MAXIMUM AT 400 PCT 20.000 AND MINIMUM AT 600 PCT 0.400 AND MAXIMUM AT 600 PCT 10.000 AND MINIMUM AT 800 PCT 0.050 AND MAXIMUM AT 800 PCT 3.000 AND MINIMUM AT 1000 PCT 0.020 AND MAXIMUM AT 1000 PCT 2.000
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDHERMETICALLY SEALED AND SHOCK RESISTANT AND VIBRATION RESISTANT
SWITCH TERMINAL TYPEQUICK DISCONNECT, MALE
SWITCH CURRENT RATING AND TYPE IN AMPSAC 10.0 AND DC 5.0
SWITCH VOLTAGE RATING AND TYPE IN VOLTSAC 250.0 AND DC 30.0
UNPACKAGED UNIT WEIGHTOUNCES NOMINAL 6.000
FREQUENCY IN HERTZ50.0 OR 60.0
MATERIALCASE PLASTIC
THREAD SERIES DESIGNATORUN
TERMINAL TYPE AND QUANTITYQUICK DISCONNECT, MALE 4

MOE rules

MOE ruleMOE CDDate assignedPICAPICA LOAAuth collab
WG01WG01-OCT-17WG81WG
ZF01ZF01-APR-91ZF81ZF

Freight

ACTY CD
ZF

Related items

Standardization

Item standardization code
5
Orig stdzn dec
97
Dt stdzn dec
11-APR-1990
NIIN status code
0

Request a quote

Your request goes to A-DEFENSE, a US Defense supplier in Texas, who will reply by email.