Catalog item

CIRCUIT BREAKER

5925FSC
01NCB code
441-9000Item number
NIIN 01-441-9000
Request a quote
DEMIL code
A

Identification

Item name code
00136
PINC
0000136
Criticality code
X
II
0
DEMIL code
A
DEMIL integrity code
1
NIIN assigned
26-FEB-97
Precious metals indicator
A
ADP equipment code
0
Hazardous material indicator
P
ESD/EMI code
A
Schedule B export code
8536200040
Last known source of supply
SMS

Part numbers

Part numberCAGECAGE statusRNCCRNVCDocument availability codeRNAACRNSC
MIL-PRF-39019/181349
MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
A41EZZ
M39019/1-216S81349
MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
A22EZZ
MIL-C-39019/181349
MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
A59EZZB

Characteristics

THREAD PITCH DIAMETERSINCHES 0.3503 TO 0.3537
BODY STYLE
BUSHING LENGTHINCHES MAXIMUM 0.380
BODY LENGTHINCHES MAXIMUM 1.562
BODY WIDTHINCHES MAXIMUM 0.625
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MAXIMUM 0.906
MOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MAXIMUM 1.700
POLE QUANTITY1
MOUNTING FACILITY TYPE AND QUANTITYTHREADED BUSHING 1
THREAD QUANTITY PER INCH32
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLESINGLE LOCATION AMPERES AC 1.0
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSSINGLE LOCATION AC 240.0
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSSINGLE LOCATION AC 300.0
CIRCUIT PROTECTION TYPESINGLE LOCATION OVERCURRENT
TRIP RELEASE METHODSINGLE LOCATION MAGNETIC
TRIP RELEASE CHARACTERISTICSINGLE LOCATION TIME DELAY
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT115.0
ULTIMATE TRIP TIME PER POLE IN SECONDSSINGLE LOCATION MINIMUM 0.200 AND MAXIMUM 7.000
RESET METHODMANUAL
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
INTERNAL TRIP RELEASE CONFIGURATIONSINGLE LOCATION SERIES TRIP
NOMINAL THREAD SIZEINCHES 0.375
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTSINGLE LOCATION MINIMUM AT 200 PCT 0.500 AND MAXIMUM AT 200 PCT 9.000 AND MAXIMUM AT 400 PCT 0.750
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND HERMETICALLY SEALED
FREQUENCY IN HERTZ400.0
TEST DATA DOCUMENTSPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). 81349--IL-C-39019
THREAD SERIES DESIGNATORUNEF
TERMINAL TYPE AND QUANTITYSCREW 4
SPECIFICATION/STANDARD DATAGOVERNMENT SPECIFICATION 81349--IL-C-39019 TO 216S

MOE rules

MOE ruleMOE CDDate assignedPICAPICA LOAAuth collab
ZG01ZG01-OCT-02ZG81ZG
ZU01ZU01-MAY-08ZU81ZU

Freight

ACTY CD
TH
NMFC
061700
NMFC sub
Z
Uniform freight class
34580
Less than truckload
W
Water commodity code
72D
Type of cargo code
Z
Special handling code
9
Air dimension code
A
Air commodity code
HZ
NMF description
ELEC APPLIANCES/INSTRUMENTS NOI

Related items

Standardization

Item standardization code
3
Orig stdzn dec
TX
Dt stdzn dec
17-AUG-2010
NIIN status code
0

Request a quote

Your request goes to A-DEFENSE, a US Defense supplier in Texas, who will reply by email.