Catalog item

CIRCUIT BREAKER

5925FSC
01NCB code
518-1198Item number
NIIN 01-518-1198
Request a quote
DEMIL code
A

Identification

Item name code
00136
PINC
0000136
Criticality code
X
II
0
DEMIL code
A
DEMIL integrity code
1
NIIN assigned
02-MAR-04
Precious metals indicator
A
ADP equipment code
0
Hazardous material indicator
P
ESD/EMI code
A
Schedule B export code
8536200040

Part numbers

Part number
AP-112-1R-62-103
CAGE
81541
SENSATA TECHNOLOGIES MARYLAND, INC
CAGE status
A
RNCC
3
RNVC
2
Document availability code
4
RNAAC
9Z
RNFC
4
RNSC
A
RNJC
3

Characteristics

THREAD PITCH DIAMETERSINCHES 0.3503 TO 0.3537
BODY STYLE
BUSHING LENGTHINCHES NOMINAL 0.330
BODY LENGTHINCHES MAXIMUM 1.562
BODY WIDTHINCHES MAXIMUM 1.937
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MAXIMUM 0.906
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 0.625
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
FRAGILITY FACTORMODERATELY RUGGED
MOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MAXIMUM 1.828
POLE QUANTITY3
ARC QUENCHING METHODMAGNETIC BLOWOUT
MOUNTING FACILITY TYPE AND QUANTITYTHREADED BUSHING WITH PANEL SEAL 1
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SPECIAL HANDLING FEATUREMAGNETIC
THREAD QUANTITY PER INCH32
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 10.0 AND AMPERES DC 10.0
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 240.0 AND DC 50.0
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 300.0 AND DC 500.0
CIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
TRIP RELEASE METHODALL LOCATIONS MAGNETIC
TRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT115.0
RESET METHODMANUAL
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO
AUXILIARY SWITCH FUNCTION AND QUANTITYALARM 1
INTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
NOMINAL THREAD SIZEINCHES 0.375
SWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE THREE
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 0.850 AND MAXIMUM AT 200 PCT 1.500
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND HERMETICALLY SEALED
SWITCH TERMINAL TYPETAB, SOLDER LUG
SWITCH CURRENT RATING AND TYPE IN AMPSAC 0.5 AND DC 0.5
SWITCH VOLTAGE RATING AND TYPE IN VOLTSAC 120.0 AND DC 50.0
UNPACKAGED UNIT WEIGHTGRAMS NOMINAL 150.0
FREQUENCY IN HERTZ400.0
TEST DATA DOCUMENTSPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). 81349--IL-C-39019
THREAD SERIES DESIGNATORUNEF
TERMINAL TYPE AND QUANTITYWIRE HOOK 6
SPECIFICATION/STANDARD DATAGOVERNMENT SPECIFICATION 81349--IL-C-39019 TO 6

MOE rules

MOE ruleMOE CDDate assignedPICAPICA LOAAuth collab
ZG01ZG01-MAR-09ZG81ZG
ZN01ZN01-MAR-04ZN81ZN

Freight

ACTY CD
30

Related items

Standardization

Item standardization code
5
Orig stdzn dec
97
Dt stdzn dec
02-MAR-2004
NIIN status code
0

Request a quote

Your request goes to A-DEFENSE, a US Defense supplier in Texas, who will reply by email.