Catalog item
Request a quoteCIRCUIT BREAKER
5925FSC
01NCB code
583-6550Item number
NIIN 01-583-6550
- DEMIL code
- A
Identification
- Item name code
- 00136
- PINC
- 0000136
- Criticality code
- X
- II
- 0
- DEMIL code
- A
- DEMIL integrity code
- 1
- NIIN assigned
- 31-MAR-10
- Precious metals indicator
- A
- ADP equipment code
- 0
- Hazardous material indicator
- P
- ESD/EMI code
- A
- Schedule B export code
- 8536200040
Part numbers
- Part number
- APGN-66-28039-1
- CAGE
- 81349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
- CAGE status
- A
- RNCC
- 2
- RNVC
- 2
- Document availability code
- E
- RNAAC
- 9Z
- RNFC
- 4
- RNSC
- D
Characteristics
| THREAD PITCH DIAMETERS | INCHES 0.4752 TO 0.4787 |
|---|---|
| BODY STYLE | |
| BUSHING LENGTH | INCHES NOMINAL 0.625 |
| BODY LENGTH | INCHES NOMINAL 2.000 |
| BODY WIDTH | INCHES NOMINAL 2.250 |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES NOMINAL 1.530 |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | INCHES NOMINAL 0.750 |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | INCHES MAXIMUM 2.232 |
| POLE QUANTITY | 3 |
| MOUNTING FACILITY TYPE AND QUANTITY | THREADED BUSHING WITH PANEL SEAL 1 |
| THREAD QUANTITY PER INCH | 32 |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | ALL LOCATIONS AMPERES AC 20.0 |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | ALL LOCATIONS AC 250.0 |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | ALL LOCATIONS AC 3500.0 |
| CIRCUIT PROTECTION TYPE | ALL LOCATIONS OVERCURRENT |
| TRIP RELEASE METHOD | ALL LOCATIONS MAGNETIC-HYDRAULIC |
| AUXILIARY TRIP COIL VOLTAGE TYPE AND RATING IN VOLTS | FIRST LOCATION AC NOMINAL 115.0 |
| TRIP RELEASE CHARACTERISTIC | ALL LOCATIONS INSTANTANEOUS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 115.0 |
| RESET METHOD | MANUAL |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 1 |
| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| INTERNAL TRIP RELEASE CONFIGURATION | THIRD LOCATION SERIES TRIP |
| NOMINAL THREAD SIZE | INCHES 0.500 |
| TRIP RELEASE DUTY CYCLE | FIRST LOCATION CONTINUOUS |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | ALL LOCATIONS MINIMUM AT 200 PCT 0.150 AND MAXIMUM AT 200 PCT 3.000 |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | SHOCK RESISTANT AND VIBRATION RESISTANT AND SALT SPRAY PROOF AND MOISTURE RESISTANT |
| SPECIAL FEATURES | RELAY COIL AT POLE ONE IS INSTANEOUS TRIP |
| FREQUENCY IN HERTZ | 50.0 OR 60.0 |
| MATERIAL | CASE PLASTIC |
| THREAD SERIES DESIGNATOR | UN |
| TERMINAL TYPE AND QUANTITY | TAB W/SCREW 8 |
MOE rules
- MOE rule
- ZH01
- MOE CD
- ZH
- Date assigned
- 01-JUN-11
- PICA
- ZH
- PICA LOA
- 81
- Auth collab
- ZH
Freight
- ACTY CD
- ZH
Related items
Standardization
- Item standardization code
- 5
- Orig stdzn dec
- 97
- Dt stdzn dec
- 31-MAR-2010
- NIIN status code
- 0
Request a quote
Your request goes to A-DEFENSE, a US Defense supplier in Texas, who will reply by email.